Kohler SB-616 Shutdown Test Box
Add products/generator-diag/hero.jpg
Generator Service Equipment

Kohler SB-616 Shutdown Test Box

Designed to aid in shutdown testing on Kohler generators in accordance with Service Bulletin SB-616. The test box provides a convenient, repeatable way to perform pre-low / low oil pressure and high / low coolant temperature shutdown testing during service and diagnostic procedures.

Price$600.00
StatusBuilt to order
ApplicationKohler SB-616 shutdown testing
Pressure TestingPre-low / low oil pressure
Temperature TestingHigh / low coolant temperature
Included Leads4 pigtail leads + red crossover cable for Test Methods 4 & 5
$600.00
Request Information / Order
Product gallery

Product details

Detailed views of the SB-616 test box, controls, enclosure, and construction.

SB-616 Shutdown Testing

Built specifically to aid with the oil-pressure and coolant-temperature shutdown checks called for by Kohler Service Bulletin SB-616.

Common Sensor Connections

Includes connector pigtails for common 2-wire and 3-wire sensor connections to simplify hookup during testing.

Universal Test Lead

A universal alligator-clip pigtail is included for applications where a direct sensor connector cannot be used.

Included pigtail leads

Included sensor/test leads & crossover cable

Each test box includes four removable pigtail leads for common generator sensor/test connections, plus a dedicated red crossover cable used with Test Methods 4 and 5.

Pressure-Sensor Pigtail

Ballenger CONN-85963 pressure-sensor pigtail for compatible generator pressure-sensor connections.

2-Way GT150 Pigtail

Ballenger CONN-85646 2-way GT150 pigtail for compatible 2-wire sensor connections.

EV1 Sensor Pigtail

EV1-style sensor pigtail for compatible generator sensor connections.

Universal Alligator-Clip Pigtail

Universal test lead using Mueller BU-55 and BU-60 alligator clips for applications where a direct sensor connector is not used.

Red Crossover Cable — Methods 4 & 5

Dedicated red crossover lead for SB-616 Test Methods 4 and 5. The matching test numbers on the box face are printed in red as a quick visual reminder to use this cable for those two procedures.

SB-616 test coverage

Specific test methods supported by this box

The controls, included pigtails and dedicated crossover lead are configured to support the applicable oil-pressure and coolant-temperature fault simulations used in SB-616 Test Methods 2, 3, 4, 5, 16 and 17.

Test Method 2

Combined Sensor Fault Simulation

Uses the 5 kΩ control to simulate applicable sensor resistance changes in the SB-616 coolant-temperature / oil-pressure test arrangement.

Test Method 3

500 Ω Coolant Temperature Test

Uses the 500 Ω control to simulate coolant-temperature sensor resistance and verify the applicable warning or shutdown response.

Test Method 4 · Red Cable

5 kΩ Oil Pressure Test

Uses the 5 kΩ control to simulate oil-pressure sensor resistance and verify the applicable low-oil-pressure fault or shutdown response. Use the included red crossover cable for this test.

Test Method 5 · Red Cable

Resistor-Network Coolant Temperature Test

Uses the 5 kΩ control together with the required 47 Ω and 22 kΩ resistor network to simulate the applicable coolant-temperature fault conditions. Use the included red crossover cable for this test.

Test Method 16

500 Ω Low Oil Pressure Test

Uses the 500 Ω control between the sensor lead and engine-block ground to simulate a low-oil-pressure fault until the generator reaches its shutdown response.

Test Method 17

High / Low Coolant Temperature Test

Uses the 5 kΩ control in both directions: one direction to simulate high coolant temperature through shutdown, and the opposite direction to produce the low-coolant-temperature fault.

Red crossover cable cue: Test Methods 4 and 5 use the included red crossover cable. The 4 and 5 markings on the test-box face are also printed in red to provide the same visual cue at the equipment.
SB-616 reference: A publicly available older revision of Kohler Service Bulletin SB-616 can be viewed at Fire Electronics (third-party PDF). This linked copy is outdated and does not contain later test methods such as Methods 16 and 17. It is provided only as a public historical/reference copy. Always use the latest Kohler service literature and model-specific diagnostic information when performing generator testing.
Product note: Designed to aid technicians performing the applicable shutdown tests described in Kohler Service Bulletin SB-616. Kohler is a trademark of its respective owner. Colvin Labs™ is not affiliated with or endorsed by Kohler.